Unlock AI power-ups — upgrade and save 20%!
Use code STUBE20OFF during your first month after signup. Upgrade now →

By Pencari Ilmu
Published Loading...
N/A views
N/A likes
System Parameters and Base Calculations
📌 The discussion focuses on setting overcurrent relays (IDMT - Inverse Definite Minimum Time) for the main substation connecting 150 kV to 20 kV.
⚙️ Base calculations were performed for and for both 20 kV (, ) and 150 kV sides (, ).
⚡ Transformer data included a rating of with 12.5% impedance, resulting in (positive sequence) of based on the system MVA.
📊 Current Transformer (CT) ratios were established: side ($150/1$), incoming side ($1000/1$), feeder side ($600/1$), and coupling substation ($600/1$).
Short Circuit Current Calculations
💡 Three-phase short circuit current () at the bus (0 km) was calculated to be .
🔌 Cable impedance calculations for a feeder resulted in a positive sequence impedance of per unit.
📉 Two-phase short circuit current () at the bus was found to be , and at the bus, it was (for a fault location).
Overcurrent Relay (OCR) Setting - Side (Incoming)
🎯 The pickup current setting () for the inverse time relay was set at $1.2$ times the nominal transformer secondary current, resulting in (secondary side).
⏱️ The maximum permissible Time Operating Relay setting () based on IEC standards for this relay is ; a setting of was chosen for safety.
✅ Using the IDMT formula with and , the Time Multiplier Setting () calculated to be .
⚡ A definite time high-set (instantaneous) setting was also defined for the side, tripping at in to handle severe short circuits.
Grading and Coordination Settings
⬆️ The relay was set to , chosen to be (greater than plus the required grading margin of ) to ensure downstream protection trips first.
🔻 The Feeder relay (downstream of incoming) was set with (faster than the relay's coordination time) resulting in (Inverse Time).
🔥 The Coupling Substation relay utilized an instantaneous high-set trip ( definite time) for severe faults, built upon an IDMT base setting with .
Key Points & Insights
➡️ The coordination check confirmed that relay trip curves do not overlap, ensuring proper sequence: Coupling Substation trips first, followed by the Feeder, then the incoming relay, and finally the relay.
➡️ The selection of for downstream relays must be faster than the next upstream relay, incorporating a minimum grading margin of .
➡️ Protection coordination involves setting both Inverse Time (IDMT) protection (for moderate faults) and Definite Time/High-Set protection (for severe, instantaneous clearing) at various levels.
📸 Video summarized with SummaryTube.com on Nov 19, 2025, 11:49 UTC
Find relevant products on Amazon related to this video
As an Amazon Associate, we earn from qualifying purchases
Full video URL: youtube.com/watch?v=yohS3tR8CJk
Duration: 35:32

Summarize youtube video with AI directly from any YouTube video page. Save Time.
Install our free Chrome extension. Get expert level summaries with one click.