Unlock AI power-ups — upgrade and save 20%!
Use code STUBE20OFF during your first month after signup. Upgrade now →
By Pencari Ilmu
Published Loading...
N/A views
N/A likes
Get instant insights and key takeaways from this YouTube video by Pencari Ilmu.
System Parameters and Base Calculations
📌 The discussion focuses on setting overcurrent relays (IDMT - Inverse Definite Minimum Time) for the main substation connecting 150 kV to 20 kV.
⚙️ Base calculations were performed for and for both 20 kV (, ) and 150 kV sides (, ).
⚡ Transformer data included a rating of with impedance, resulting in (positive sequence) of based on the system MVA.
📊 Current Transformer (CT) ratios were established: side ($150/1$), incoming side ($1000/1$), feeder side ($600/1$), and coupling substation ($600/1$).
Short Circuit Current Calculations
💡 Three-phase short circuit current () at the bus (0 km) was calculated to be .
🔌 Cable impedance calculations for a feeder resulted in a positive sequence impedance of per unit.
📉 Two-phase short circuit current () at the bus was found to be , and at the bus, it was (for a fault location).
Overcurrent Relay (OCR) Setting - Side (Incoming)
🎯 The pickup current setting () for the inverse time relay was set at $1.2$ times the nominal transformer secondary current, resulting in (secondary side).
⏱️ The maximum permissible Time Operating Relay setting () based on IEC standards for this relay is ; a setting of was chosen for safety.
✅ Using the IDMT formula with and , the Time Multiplier Setting () calculated to be .
⚡ A definite time high-set (instantaneous) setting was also defined for the side, tripping at in to handle severe short circuits.
Grading and Coordination Settings
⬆️ The relay was set to , chosen to be (greater than plus the required grading margin of ) to ensure downstream protection trips first.
🔻 The Feeder relay (downstream of incoming) was set with (faster than the relay's coordination time) resulting in (Inverse Time).
🔥 The Coupling Substation relay utilized an instantaneous high-set trip ( definite time) for severe faults, built upon an IDMT base setting with .
Key Points & Insights
➡️ The coordination check confirmed that relay trip curves do not overlap, ensuring proper sequence: Coupling Substation trips first, followed by the Feeder, then the incoming relay, and finally the relay.
➡️ The selection of for downstream relays must be faster than the next upstream relay, incorporating a minimum grading margin of .
➡️ Protection coordination involves setting both Inverse Time (IDMT) protection (for moderate faults) and Definite Time/High-Set protection (for severe, instantaneous clearing) at various levels.
📸 Video summarized with SummaryTube.com on Nov 19, 2025, 11:49 UTC
Find relevant products on Amazon related to this video
As an Amazon Associate, we earn from qualifying purchases
Full video URL: youtube.com/watch?v=yohS3tR8CJk
Duration: 35:30
Get instant insights and key takeaways from this YouTube video by Pencari Ilmu.
System Parameters and Base Calculations
📌 The discussion focuses on setting overcurrent relays (IDMT - Inverse Definite Minimum Time) for the main substation connecting 150 kV to 20 kV.
⚙️ Base calculations were performed for and for both 20 kV (, ) and 150 kV sides (, ).
⚡ Transformer data included a rating of with impedance, resulting in (positive sequence) of based on the system MVA.
📊 Current Transformer (CT) ratios were established: side ($150/1$), incoming side ($1000/1$), feeder side ($600/1$), and coupling substation ($600/1$).
Short Circuit Current Calculations
💡 Three-phase short circuit current () at the bus (0 km) was calculated to be .
🔌 Cable impedance calculations for a feeder resulted in a positive sequence impedance of per unit.
📉 Two-phase short circuit current () at the bus was found to be , and at the bus, it was (for a fault location).
Overcurrent Relay (OCR) Setting - Side (Incoming)
🎯 The pickup current setting () for the inverse time relay was set at $1.2$ times the nominal transformer secondary current, resulting in (secondary side).
⏱️ The maximum permissible Time Operating Relay setting () based on IEC standards for this relay is ; a setting of was chosen for safety.
✅ Using the IDMT formula with and , the Time Multiplier Setting () calculated to be .
⚡ A definite time high-set (instantaneous) setting was also defined for the side, tripping at in to handle severe short circuits.
Grading and Coordination Settings
⬆️ The relay was set to , chosen to be (greater than plus the required grading margin of ) to ensure downstream protection trips first.
🔻 The Feeder relay (downstream of incoming) was set with (faster than the relay's coordination time) resulting in (Inverse Time).
🔥 The Coupling Substation relay utilized an instantaneous high-set trip ( definite time) for severe faults, built upon an IDMT base setting with .
Key Points & Insights
➡️ The coordination check confirmed that relay trip curves do not overlap, ensuring proper sequence: Coupling Substation trips first, followed by the Feeder, then the incoming relay, and finally the relay.
➡️ The selection of for downstream relays must be faster than the next upstream relay, incorporating a minimum grading margin of .
➡️ Protection coordination involves setting both Inverse Time (IDMT) protection (for moderate faults) and Definite Time/High-Set protection (for severe, instantaneous clearing) at various levels.
📸 Video summarized with SummaryTube.com on Nov 19, 2025, 11:49 UTC
Find relevant products on Amazon related to this video
As an Amazon Associate, we earn from qualifying purchases

Summarize youtube video with AI directly from any YouTube video page. Save Time.
Install our free Chrome extension. Get expert level summaries with one click.